AQUATANK
Water tanks built from ST 37 hot-dip galvanized steel sheet as 1080 × 1080 mm modular panels cold-formed on high-pressure presses, produced in the required capacity. Galvanized tanks are manufactured to national and international standards, with TSEK and CE certification.
Why a Galvanized Water Tank?
GALVANIZED WATER TANK
Galvanized Water Tank Top View
Galvanized Water Tank Front View
Height Configurations
Capacity and Dimension Table
GALVANIZED STEEL WATER TANKS
A hot-dip galvanized sectional water tank is a rectangular tank built on site by bolting together 1,080 × 1,080 mm pressed panels made from ST 37 steel with a hot-dip galvanized finish (catalogue pp. 4, 14). The same product is often called a galvanized panel tank, a pressed steel sectional tank or a modular galvanized water tank. In the Aquatank range it belongs to the "Modular Steel Water Tanks" family, alongside the stainless steel tank.
Because the tank arrives as a kit of panels rather than a one-piece vessel, it can be sized to the room, carried through narrow doorways and assembled indoors where a factory-built tank would not fit (catalogue p. 4).
The panels are pressed from ST 37 steel sheet, and corrosion protection comes from hot-dip galvanizing (catalogue pp. 4, 14). In hot-dip galvanizing the steel is dipped into a bath of molten zinc, leaving a zinc coating metallurgically bonded to the steel surface.
The coating protects the steel in two ways. First, it is a barrier that keeps moisture and oxygen away. Second, where the surface gets scratched, the zinc corrodes first and sacrificially protects the exposed steel. This protection lasts only as long as the zinc layer remains, so the coating should not be damaged during assembly and maintenance.
Galvanized panels measure 1,080 × 1,080 mm, tank heights run from 540 mm to 4,320 mm in 540 mm steps, and the standard capacity range is 1.26–90 m³ (catalogue pp. 15, 16).
The sizes below are standard steel tank layouts taken from our catalogue (p. 15). Dimensions are width × length × height in centimetres; the panel layout shows how many 108 cm panels are used in each direction.
| Capacity (m³) | Size (cm) W × L × H | Panel layout |
|---|---|---|
| 1.26 | 108 × 108 × 108 | 1 × 1 × 1 |
| 2.50 | 108 × 216 × 108 | 1 × 2 × 1 |
| 2.50 | 108 × 108 × 216 | 1 × 1 × 2 |
| 5.00 | 216 × 216 × 108 | 2 × 2 × 1 |
| 5.00 | 216 × 108 × 216 | 2 × 1 × 2 |
| 7.50 | 324 × 108 × 216 | 3 × 1 × 2 |
| 10.00 | 216 × 216 × 216 | 2 × 2 × 2 |
| 15.00 | 324 × 216 × 216 | 3 × 2 × 2 |
| 20.00 | 432 × 216 × 216 | 4 × 2 × 2 |
| 22.50 | 324 × 324 × 216 | 3 × 3 × 2 |
| 25.00 | 540 × 216 × 216 | 5 × 2 × 2 |
| 30.00 | 324 × 432 × 216 | 3 × 4 × 2 |
| 40.00 | 432 × 432 × 216 | 4 × 4 × 2 |
| 50.00 | 540 × 432 × 216 | 5 × 4 × 2 |
| 90.00 | 648 × 432 × 324 | 6 × 4 × 3 |
The same volume can take different shapes. A 5 m³ tank, for example, can be built low at 216 × 216 × 108 cm or narrow at 216 × 108 × 216 cm (catalogue p. 15), which helps when ceiling height or floor space is limited.
For gross volumes of the steel layouts and GRP tank dimensions, see our guide to sectional water tank sizes.
Galvanized sectional tanks are used for fire water reserves, process water and other water that is not for drinking or domestic use. The TSEK certificate shown in our catalogue lists the galvanized modular tank as not intended for drinking or domestic-use water (catalogue p. 21).
Storing drinking water? Choose a GRP sectional tank or a stainless steel water tank instead of galvanized steel. What to look for in a drinking water tank: drinking water storage tanks. Our documents are listed on the Certificates page.
The main reasons to specify galvanized steel are strength, cost and flexible sizing (catalogue pp. 4, 15).
A galvanized sectional tank stands on a concrete base, with at least 50 cm left between the tank and any wall, column or ceiling for assembly and maintenance access (catalogue pp. 9, 16).
Worked example: a 10 m³ tank measuring 216 × 216 × 216 cm, with walls or columns on all four sides, needs a clear floor area of at least 316 × 316 cm (216 + 50 + 50 cm). The ceiling must be no lower than the tank height plus the base height plus 50 cm of top clearance.
After installation, periodic maintenance covers cleaning, disinfection and inspection at regular intervals (catalogue p. 18).
For the base, panel assembly and pipe connections step by step, see sectional water tank installation.
The first question is what the water is for: GRP or stainless steel for drinking and domestic-use water, galvanized steel for fire and process water.
| Feature | Galvanized | GRP | Stainless steel |
|---|---|---|---|
| Material | ST 37 hot-dip galvanized steel | Glass fibre reinforced composite | AISI 304 / 316 L stainless steel |
| Panel | 1,080 × 1,080 mm | 1,000 × 1,000 mm | 1,080 × 1,080 mm |
| Height | 540–4,320 mm | 1.0–5.0 m | 540–4,320 mm |
| Key feature (catalogue) | High strength, economical solution | Opaque, algae-free, suitable for outdoor use | Highest hygiene, corrosion resistance |
| Our recommended use | Fire water, process and non-potable water | Drinking water, outdoor installations | Drinking and domestic-use water, hygiene-critical buildings |
Source: catalogue pp. 4, 21. Not sure which material fits? Send the capacity, room dimensions and intended use through the quote form and we will propose the material and layout. For a detailed comparison of the three materials, see GRP vs stainless steel vs galvanized water tanks.
A galvanized tank is for water that is not for drinking or domestic use, such as fire water reserves and process water. The TSEK certificate shown in our catalogue lists the galvanized modular tank as not intended for drinking or domestic-use water (catalogue p. 21), so we do not recommend galvanized tanks for drinking water. For potable or domestic-use water choose a GRP or stainless steel tank. Our guide GRP vs stainless steel vs galvanized water tanks explains which material suits which water.
The standard 10 m³ galvanized tank in our catalogue measures 216 × 216 × 216 cm, two panels in each direction (catalogue p. 15). With walls on all four sides and the minimum 50 cm clearance, allow a clear area of at least 316 × 316 cm (catalogue p. 16). Other width, length and height combinations can be designed to fit your room.
The tallest galvanized tank is 4,320 mm (4.32 m), with heights chosen in 540 mm steps (catalogue p. 16). The standard capacity range is 1.26–90 m³. The catalogue states that intermediate sizes and custom capacities are produced to project requirements; needs outside the standard range are assessed at the quotation stage (catalogue p. 15).
Yes. The galvanized tank is intended for water other than drinking or domestic-use water (catalogue p. 21), and a fire water reserve is one such use. The volume is set by the project's fire protection design, and we can supply the tank together with the fire pump set (catalogue p. 22).
Yes. The tank is delivered as panels and bolted together on site, so it can pass through narrow access doors (catalogue p. 4). When you request a quote we ask for the width of the door or opening the panels will pass through (catalogue p. 23).
The main factors are capacity and dimensions (and therefore the number of panels), tank height, installation location (indoors, rooftop or outdoors), access width, intended use and the project address. Send these details through the quote form and we will price the tank for your project (catalogue p. 23). Each factor is explained in our guide to sectional water tank prices.
The catalogue states a 2-year product warranty (catalogue pp. 3, 18). Panels, gaskets and fasteners are supplied from stock, faults and leaks are dealt with promptly, and periodic maintenance covering cleaning, disinfection and inspection is available (catalogue p. 18).
Plan an online meeting with our experts to learn about modular water storage technologies and get a project and price quote.
Get a Quote!We use cookies to improve our website and measure our advertising. If you accept, analytics and advertising cookies are enabled; if you decline, only essential cookies are used. Cookie Policy